您的浏览器版本过低,为保证更佳的浏览体验,请点击更新高版本浏览器

以后再说X

Pepperl+Fuchs

SMART Transmitter Power Supply KCD2-STC-Ex1.2O

  • 1-channel isolated barrier

  • 24 V DC supply (Power Rail)

  • Input for 2-wire SMART transmitters and current sources

  • Signal splitter (1 input and 2 outputs)

  • Dual output 0/4 mA ... 20 mA or 0/1 V ... 5 V

  • Terminal blocks with test sockets

  • Up to SIL 2 (SC 3) acc. to IEC/EN 61508


INQUIRY

技术参数节选  KCD2-STC-Ex1.2O

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3
Supply
ConnectionPower Rail or terminals 9+, 10-
Rated voltage19 ... 30 V DC
Ripplewithin the supply tolerance
Power dissipationapprox. 1.4 W at 20 mA transfer current, 250 Ω in both outputs
Power consumption2 W
Input
Connection sidefield side
Connectionterminals 1+, 2- (sink); 3+, 4- (source)
Input signal0/4 ... 20 mA
Voltage dropterminals 3, 4: ≤ 6.1 V at 20 mA
Short-circuit currentterminals 1+, 2-: 25 mA
Input resistanceterminals 1+, 2-: max. 500 Ω (BRAIN)
(250 Ω load)
Available voltageterminals 1+, 2-: ≥ 16 V at 20 mA , ≥ 18.5 V at 4 mA
Output
Connection sidecontrol side
Connectionsource: terminals 5-, 6+; 7-, 8+
sink: terminals 5+, 6-, 7+, 8-
Loadchannel 1: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)
channel 2: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)
Output signal0/4 ... 20 mA or 0/1 ... 5 V
Ripplemax. 50 µA rms
Transfer characteristics
DeviationIout < 20 µA (0.1 %); Vout < 10 mV (0.2 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V

Influence of ambient temperaturecurrent output: 0.25 µA/K
voltage output: 80 µV/K
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 6 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 6 kHz (-3 dB)
Settling time6 ms
Rise time/fall time2 ms
Galvanic isolation
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Output/Outputfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elementsLED
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility

Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012
EN 61326-3-2:2008
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 13 ATEX 0077 X

MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I

Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Supply

Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
Equipmentterminals 1+, 2-

Voltage25.2 V

Voltage28.2 V

Current93 mA

Power656 mW

Internal capacitance10 nF

Internal inductance0 mH
Equipmentterminals 3+, 4-

Voltage30 V

Current115 mA

Power700 mW

Voltage5 V

Current6.8 mA

Power1.6 mW
Output

Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificateBASEEFA 13 ATEX 0078 X

MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation

Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V

Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity

Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approval

Control drawing116-0380 (cULus)
IECEx approval

IECEx certificateIECEx BAS 13.0043X

IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
NoteBoth output loads must be connected to ensure complete and correct operation within the technical specification.
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.


Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514


Related Products

Products

Contact Us

Contact:Zhang jessica Add: 807 Zhujiaqiao, Dahong Village, Malu Town, Jiading District, Shanghai, China中国上海, Phone: +86 13916215712 Mailbox:jessica.IND.CN.SHH@gmail.com WeChat:+86 13916215712 WhatsApp:+86 13916215712 Skype:jessica.IND.CN.SHH@gmail.com Faceboo:https://www.facebook.com/profile.php?id=61550040507450&mibextid=ZbWKwL Linkedin:https://www.linkedin.com/in/张-西霞-jessica
Online Service
Contact information

Hotline

+8613916215712

Work shift

from Monday to Friday

Company telephone

+8613916215712

QR code