您的浏览器版本过低,为保证更佳的浏览体验,请点击更新高版本浏览器

以后再说X

Pepperl+Fuchs

Universal Temperature Converter KFD2-UT2-Ex2

  • 2-channel isolated barrier

  • 24 V DC supply (Power Rail)

  • Thermocouple, RTD, potentiometer or voltage input

  • Usable as signal splitter (1 input and 2 outputs)

  • Current output 0/4 mA ... 20 mA

  • Sink or source mode

  • Configurable by PACTware

  • Line fault (LFD) and sensor burnout detection

  • Up to SIL 2 acc. to IEC/EN 61508 / IEC/EN 61511


INQUIRY

技术参数节选  KFD2-UT2-Ex2

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Connectionterminals 14+, 15- or power feed module/Power Rail
Rated voltage20 ... 30 V DC
Ripplewithin the supply tolerance
Power dissipation≤ 1.53 W
Power consumptionmax. 1.53 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectionterminals 1, 2, 3; 4, 5, 6
RTDtype Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)

Measuring currentapprox. 200 µA with RTD

Types of measuring2-, 3-wire connection

Lead resistancemax. 50 Ω per line

Measurement loop monitoringsensor breakage, sensor short-circuit
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)

Cold junction compensationexternal and internal

Measurement loop monitoringsensor breakage
Potentiometer0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
Voltageselectable within the range -100 ... 100 mV
Input resistance≥ 1 MΩ (-100 ... 100 mV)
Output
Connection sidecontrol side
Connectionoutput I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-)
output II: terminal 10: source (-), sink (+), terminal 11: source (+), terminal 12: sink(-)
Output I, IIAnalog current output

Current range0 ... 20 mA or 4 ... 20 mA

Fault signaldownscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)

Sourceload 0 ... 550 Ω
open-circuit voltage ≤ 18 V

SinkVoltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V,
series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage.
The maximum value of the resistance is (V - 5)/0.0215 Ω.
Transfer characteristics
Deviation

After calibrationPt100: ± (0.06 % of measurement value in K + 0.1 % of span + 0.1 K (4-wire connection))
thermocouple: ± (0.05 % of measurement value in °C + 0.1 % of span + 1 K (1.2 K for types R and S)) , includes ± 0.8 K fault of the cold junction compensation (CJC)
mV: ± (50 µV + 0.1 % of span)
potentiometer: ± (0.05 % of full scale + 0.1 % of span, (excludes faults due to lead resistance))

Influence of ambient temperaturePt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔTamb*)
thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔTamb*)), influence of cold junction compensation (CJC) included
mV: ± (0.01 % of measurement value + 0.006 % of span)/K ΔTamb*)
potentiometer: ± 0.006 % of span/K ΔTamb*)
*) ΔTamb = ambient temperature change referenced to 23 °C (296 K)

Influence of supply voltage< 0.01 % of span

Influence of load≤ 0.001 % of output value per 100 Ω
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1.2 s, thermocouples with CJC: 1.4 s, thermocouples with fixed ref. temp: 1.4 s, 3- or 4-wire RTD: 1.1 s, 2-wire RTD: 920 ms, Potentiometer: 3-wire connection 2.8 s, 2-wire connection 2.25 s
Galvanic isolation
Output/supply, programming inputfunctional insulation, rated insulation voltage 50 V AC
There is no electrical isolation between the programming input and the supply.
The programming cable provides galvanic isolation so that ground loops are avoided.
Indicators/settings
Display elementsLEDs
Configurationvia PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility

Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2004
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 130 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateCESI 04 ATEX 143

MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I

InputEx ia
Inputsterminals 1, 2, 3, 4, 5, 6 (for passive equipment)

Voltage Uo9 V

Current Io22 mA

Power Po50 mW
Analog outputs, power supply, collective error

Maximum safe voltage250 V (Attention! This is not the rated voltage.)
Interface

Maximum safe voltage250 V (Attention! The rated voltage is lower.), RS 232
CertificateTÜV 02 ATEX 1797 X

MarkingEx-Hexagon II 3G Ex nA II T4
Galvanic isolation

Input/Other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity

Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
International approvals
UL approval

Control drawing116-0410
CSA approval

Control drawing116-0314 (cCSAus)
116-0347
IECEx approval

IECEx certificateIECEx TUN 07.0003
IECEx CML 16.0126X

IECEx marking[Ex ia Ga] IIC
[Ex ia Da] IIIC
[Ex ia Ma] I
Ex nA IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.


Classifications

SystemClasscode
ECLASS 13.027210129
ECLASS 12.027210129
ECLASS 11.027210129
ECLASS 10.0.127210129
ECLASS 9.027210129
ECLASS 8.027210190
ECLASS 5.127210107
ETIM 9.0EC002919
ETIM 8.0EC002919
ETIM 7.0EC002919
ETIM 6.0EC002919
ETIM 5.0EC001485
UNSPSC 12.132101514


Related Products

Products

Contact Us

Contact:Zhang jessica Add: 807 Zhujiaqiao, Dahong Village, Malu Town, Jiading District, Shanghai, China中国上海, Phone: +86 13916215712 Mailbox:jessica.IND.CN.SHH@gmail.com WeChat:+86 13916215712 WhatsApp:+86 13916215712 Skype:jessica.IND.CN.SHH@gmail.com Faceboo:https://www.facebook.com/profile.php?id=61550040507450&mibextid=ZbWKwL Linkedin:https://www.linkedin.com/in/张-西霞-jessica
Online Service
Contact information

Hotline

+8613916215712

Work shift

from Monday to Friday

Company telephone

+8613916215712

QR code