您的浏览器版本过低,为保证更佳的浏览体验,请点击更新高版本浏览器

以后再说X

Pepperl+Fuchs

SMART Transmitter Power Supply KCD2-STC-Ex1

  • 1-channel isolated barrier

  • 24 V DC supply (Power Rail)

  • Input for 2-wire SMART transmitters and current sources

  • Output for 4 mA ... 20 mA or 1 V ... 5 V

  • Housing width 12.5 mm

  • Up to SIL 2 (SC 3) acc. to IEC/EN 61508


INQUIRY

技术参数节选  KCD2-STC-Ex1

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3
Supply
ConnectionPower Rail or terminals 9+, 10-
Rated voltage19 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 45 mA at 24 V and 20 mA source mode output
Power dissipation≤ 800 mW
Power consumption≤ 1.1 W
Input
Connection sidefield side
Connectionterminals 1+, 2-; 3+, 4-
Input signal4 ... 20 mA limited to approx. 26 mA
Open circuit voltage/short-circuit currentterminals 1+, 2-: 22 V / 26 mA
Voltage dropterminals 3+, 4- : approx. 5 V
Available voltageterminals 1+, 2-: ≥ 15 V at 20 mA ; ≥ 18 V at 4 mA
Output
Connection sidecontrol side
Connectionterminals 5-, 6+
terminals 5-, 8+ for HART resistor
Load0 ... 350 Ω (source mode)
Output signalsource mode: 4 ... 20 mA or 1 ... 5 V (internal resistor: 250 Ω, 0.1 %)
sink mode: 4 ... 20 mA, operating voltage 10 ... 30 V
For additional internal or external loads (e. g. terminal +8) the voltage drop has to be considered, e. g. 250 Ω x 20 mA = 5 V.
Ripple20 mV rms
Transfer characteristics
Deviationat 20 °C (68 °F)
< 0.1 % of full scale, incl. non-linearity and hysteresis (source mode and sink mode 4 ... 20 mA)
≤ ± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)

Influence of ambient temperature< 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)) (source mode and sink mode 4 ... 20mA)
< 0.5 mV/K (-20 ... 70 °C (-4 ... 158 °F)); < 1 mV/K (-40 ... -20 °C (-40 ... -4 °F)) (source mode 1...5 V)
Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Settling time≤ 50 ms
Rise time/fall time≤ 10 ms
Galvanic isolation
Input/Outputbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplybasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLED
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility

Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017
EN 61326-3-2:2018
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2019
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateCESI 06 ATEX 021 X

MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I

InputEx ia
Supply

Maximum safe voltage250 V AC (Attention! Um is no rated voltage.)
Equipmentterminals 1+, 2-

Voltage25.2 V

Current100 mA

Power630 mW

Internal capacitance5.7 nF

Internal inductancenegligible
Equipmentterminals 3+, 4-

Voltage30 V

Current128 mA

Power1000 mW

Voltage7.2 V

Current100 mA

Power25 mW

Internal capacitance5.7 nF

Internal inductancenegligible
CertificateCESI 19 ATEX 021 X

MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation

Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V

Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity

Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018
International approvals
FM approval

FM certificateFM 18 CA 0116 X , FM 19 US 0117 X

Control drawing116-0469 (cFMus)
UL approvalE106378

Control drawing116-0459 (cULus)
IECEx approval

IECEx certificateIECEx CES 06.0001X

IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.


Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514


Related Products

Products

Contact Us

Contact:Zhang jessica Add: 807 Zhujiaqiao, Dahong Village, Malu Town, Jiading District, Shanghai, China中国上海, Phone: +86 13916215712 Mailbox:jessica.IND.CN.SHH@gmail.com WeChat:+86 13916215712 WhatsApp:+86 13916215712 Skype:jessica.IND.CN.SHH@gmail.com Faceboo:https://www.facebook.com/profile.php?id=61550040507450&mibextid=ZbWKwL Linkedin:https://www.linkedin.com/in/张-西霞-jessica
Online Service
Contact information

Hotline

+8613916215712

Work shift

from Monday to Friday

Company telephone

+8613916215712

QR code