您的浏览器版本过低,为保证更佳的浏览体验,请点击更新高版本浏览器

以后再说X

Pepperl+Fuchs

Resistance Repeater KCD2-RR-Ex1

  • 1-channel isolated barrier

  • 24 V DC supply (Power Rail)

  • Resistance and RTD input (Pt100, Pt500, Pt1000)

  • Resistance output

  • Accuracy 0.1 %

  • Line fault detection (LFD) for Pt100

  • Housing width 12.5 mm

  • Up to SIL 2 acc. to IEC 61508


INQUIRY

技术参数节选  KCD2-RR-Ex1

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionPower Rail or terminals 9+, 10-
Rated voltage19 ... 30 V DC
Ripplewithin the supply tolerance
Rated current< 20 mA
Power consumption0.35 W (24 V and 1 mA sense current)
Input
Connection sidefield side
Connectionterminals 1, 2, 3, 4
Line fault detectionyes , at Pt100
Lead resistance≤ 10 % of resistance value
Transmission range0 ... 10 mA
Available voltage9 V
Line fault detection8 nA
Output
Connection sidecontrol side
Connectionterminals 5-, 7-, 6+, 8+
Current0 ... 10 mA
Available voltage0 ... 4.2 V
Fault signal< 10 Ω or > 400 Ω, depending on lead disconnected (measuring current ≤ 1 mA)
> 400 Ω, terminal 3 lead disconnected in 2-/4-wire (measuring current ≤ 0.3 mA)
Transfer characteristics
Accuracy0.1 %
Deviation4-wire
Im ≥ 1 mA: ±0.1 % of Rm or ± 0.1 Ω (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: ± 1 % of Rm or 1 Ω (the larger value is applicable).
3-wire
Im ≥ 1 mA: (±0.1 % - 0.1 Ω Offset) or ± 0.2 Ω (the larger value is applicable)
Im < 1 mA: accuracy reduces in proportion to Im.
e. g. Im = 0.1 mA: (±1 % - 0.1 Ω Offset) or ± 1.1 Ω (the larger value is applicable)

Influence of ambient temperatureIm ≥ 1 mA, Rm ≥ 100 Ω : 0.01 %/K in the range -20 ... +60 °C (253 ... 333 K)
Im < 1 mA or Rm < 100 Ω: temperature stability reduces in proportion to Im or Rm
Rise timesignal response time ≤ 2 ms (10 ... 90 %)
response to application of Im: Rm > 50 Ω and Im < 5mA: < 5ms
response to application of Im: Rm > 30 Ω and Im < 5mA: < 10ms
response to application of Im: Rm > 18 Ω and Im < 5mA: < 20ms
Galvanic isolation
Input/Outputreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation acc. to EN 50178, rated insulation voltage 300 Veff
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Indicators/settings
Display elementsLED
Control elementsDIP-switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility

Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 10 ATEX 0061

MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I

Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I

Voltage12.4 V

Current17.4 mA

Power54 mW
Supply

Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
Output

Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
CertificateBASEEFA 10 ATEX 0062X

MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation

Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11:2012, voltage peak value 375 V

Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11:2012, voltage peak value 375 V
Directive conformity

Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012
International approvals
FM approval

Control drawing116-0129 (cFMus)
UL approval

Control drawing116-0332 (cULus)
IECEx approvalIECEx BAS 10.0024
IECEx BAS 10.0025X

Approved for[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I , Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.
Accessories
Optional accessories- power feed module KFD2-EB2(.R4A.B)(.SP)
- universal power rail UPR-03(-M)(-S)
- profile rail K-DUCT-BU(-UPR-03)
- insertion bridge EBP 2- 5


Classifications

SystemClasscode
ECLASS 13.027210129
ECLASS 12.027210120
ECLASS 11.027210120
ECLASS 10.0.127210120
ECLASS 9.027210120
ECLASS 8.027210120
ECLASS 5.127210120
ETIM 9.0EC002653
ETIM 8.0EC002653
ETIM 7.0EC002653
ETIM 6.0EC002653
ETIM 5.0EC001485
UNSPSC 12.132101514


Related Products

Products

Contact Us

Contact:Zhang jessica Add: 807 Zhujiaqiao, Dahong Village, Malu Town, Jiading District, Shanghai, China中国上海, Phone: +86 13916215712 Mailbox:jessica.IND.CN.SHH@gmail.com WeChat:+86 13916215712 WhatsApp:+86 13916215712 Skype:jessica.IND.CN.SHH@gmail.com Faceboo:https://www.facebook.com/profile.php?id=61550040507450&mibextid=ZbWKwL Linkedin:https://www.linkedin.com/in/张-西霞-jessica