您的浏览器版本过低,为保证更佳的浏览体验,请点击更新高版本浏览器

以后再说X

Pepperl+Fuchs

Switch Amplifier KCD2-SR-Ex1.LB

  • 1-channel isolated barrier

  • 24 V DC supply (Power Rail)

  • Dry contact or NAMUR inputs

  • Usable as signal splitter (1 input and 2 outputs)

  • Relay contact output

  • Fault relay contact output

  • Line fault detection (LFD)

  • Housing width 12.5 mm

  • Up to SIL 2 (SC 3) acc. to IEC/EN 61508


INQUIRY

技术参数节选  KCD2-SR-Ex1.LB

General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Systematic capability (SC)SC 3
Supply
ConnectionPower Rail or terminals 9+, 10-
Rated voltage19 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 37 mA
Power dissipation≤ 750 mW
Power consumption≤ 750 mW
Input
Connection sidefield side
Connectionterminals 1+, 2-
Rated valuesacc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit currentapprox. 8 V DC / approx. 8 mA
Switching point/switching hysteresis1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detectionbreakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratiomin. 20 ms / min. 20 ms
Output
Connection sidecontrol side
Connectionoutput I: terminals 5, 6 ; output II: terminals 7, 8
Output Isignal ; relay
Output IIsignal or fault message ; relay
Contact loading250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load
Minimum switch current2 mA / 24 V DC
Energized/De-energized delay≤ 20 ms / ≤ 20 ms
Mechanical life107 switching cycles
Transfer characteristics
Switching frequency≤ 10 Hz
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility

Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage

Directive 2014/35/EUEN 61010-1:2010+A1:2019+A1:2019/AC:2019
Conformity
Electromagnetic compatibilityNE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018
Degree of protectionIEC 60529:1989+A1:1999+A2:2013
Functional safetyIEC/EN 61508:2010
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 06 ATEX 0092 X

MarkingEx-Hexagon II 3(1)G Ex ec nC [ia Ga] IIC T4 Gc , Ex-Hexagon II (1)D [Ex ia Da] IIIC , Ex-Hexagon I (M1) [Ex ia Ma] I

InputEx ia

Voltage10.5 V

Current13 mA

Power34 mW (linear characteristic)
Supply

Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
Output

Contact loadingZone 2 : 50 V AC/2 A/cos φ > 0.75; 30 V DC/2 A resistive load

Maximum safe voltage253 V AC (Attention! The rated voltage can be lower.)
Fault indication output

Maximum safe voltage40 V DC (Attention! Um is no rated voltage.)
Galvanic isolation

Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V

Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity

Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019
International approvals
UL approvalE106378

Control drawing116-0477 (cULus)
IECEx approval

IECEx certificateIECEx BAS 06.0025 X

IECEx markingEx ec nC [ia Ga] IIC T4 Gc
[Ex ia Da] IIIC
[Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.


Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514


Related Products

Products

Contact Us

Contact:Zhang jessica Add: 807 Zhujiaqiao, Dahong Village, Malu Town, Jiading District, Shanghai, China中国上海, Phone: +86 13916215712 Mailbox:jessica.IND.CN.SHH@gmail.com WeChat:+86 13916215712 WhatsApp:+86 13916215712 Skype:jessica.IND.CN.SHH@gmail.com Faceboo:https://www.facebook.com/profile.php?id=61550040507450&mibextid=ZbWKwL Linkedin:https://www.linkedin.com/in/张-西霞-jessica
Online Service
Contact information

Hotline

+8613916215712

Work shift

from Monday to Friday

Company telephone

+8613916215712

QR code